EN 13501-1:2018 Classification using data from reaction to fire tests
1. Standard - EN 13501-1:2018
EN 13501-1:2018 Fire classification of construction products and building elements-Part 1: Classification using data from reaction to fire tests. EN 13501-1:2018 replaced EN 13501-1:2007+A1:2009.
EN 13501-1 according to requirements and test results, divided into seven levels: A1, A2, B, C, D, E, F
EN13501-1 related standard:
EN ISO 1182: non –combustibility test
EN ISO 1716: heat of combustion test
EN 13823: single burning item test
EN ISO 9239-1: determination of the burning behaviour of floorings, using a radiant heat source
EN ISO 11925-2: ignitability test
2. Standard Brief-- EN 13501-1:2018
Flammability classification:A1、A2、B、C、D、E、F or AFL1、AFL2、BFL、CFL、DFL 、EFL 、FFL or AL1、AL2、BL、CL、DL 、EL 、FL
Toxicity:T0、T1、T2
Smoke density:S1、S2、S3
dripping:D0、D1、D2
3. EN 13501-1:2018 Test method and classification
3.1 Classes of reaction to fire performance for construction products excluding floorings
Class A1: According to EN ISO 1182 and EN ISO 1716; meet to the standards.
Class A2: According to EN ISO 1182、EN ISO 1716 and EN ISO 13823; meet to the standards.
Class B、C、D: According to EN ISO 13823、EN ISO 11925-2; meet to the standards.
Class E: According to EN ISO 11925-2; meet to the standards.
Class F: According to EN ISO 11925-2; fail to the standards.
3.2 Classes of reaction to fire performance for floorings
Class A1FL: According to EN ISO 1182 and ISO EN 1716; meet to the standards.
Class A2FL: According to EN ISO 1182、EN ISO 1716 and EN ISO 9239-1; meet to the standards.
Class BFL、CFL、DFL: According to EN ISO 9239-1、EN ISO 11925-2; meet to the standards.
Class EFL: According to EN ISO 11925-2; meet to the standards.
Class FFL: According to EN ISO 11925-2; meet to the standards.
3.3 Classes of reaction to fire performance for linear pipe thermal insulation products.
Class A1L: According to EN ISO 1182 and EN ISO 1716; meet to the standards.
Class A2L: According to EN ISO 1182、EN ISO 1716 and EN ISO 13823; meet to the standards.
Class BL、CL、DL: According to EN ISO 13823、EN ISO 11925-2; meet to the standards.
Class EL: According to EN ISO 11925-2; meet to the standards.
Class FL: According to EN ISO 11925-2; fail to the standards.
EN 13501-1 is similar with GB 8624:2006
Tel: (+86) 25 86583475 (+86) 400 6036575