DIN EN 61034-2: smoke density of cables
DIN EN 61034-2: smoke density of cables
DIN5510-2 Table 6(Requirements on electric cables and wires), all cable and wires according to DIN EN 61034 standard to DIN5510-2 smoke density cable testing.
DIN EN 61034/DIN5510-2 smoke density cable testing——Standard
DIN EN 61034: consists of the following part, under the general title measurement of smoke density of cables burning under defined conditions.
DIN EN 61034-1: Measurement of smoke density of cables burning under defined conditions-Part 1: Test apparatus.
DIN EN 61034-2: Measurement of smoke density of cables burning under defined conditions---Part 2: Test procedure and requirement.
EN 61034-2:2005 is identical with IEC 61034-2:2005.It supersedes BS EN 50268-2:2002 which is withdrawn.
DIN EN 61034/DIN5510-2 smoke density cable testing——test method
Smoke density test is the combustion of an important aspect of performance evaluation, as it relates to the degree of difficulty for personnel evacuation.
Cable requirements straight, before testing the temperature 23 ℃ ± 5 ℃ placed under 16 hours in advance. Experimental test time is 40 minutes, smoke density test by the lowest rate of light transmission
DIN5510-2 standard requirement
Smoke density test by the lowest rate of light transmission≥60%.
DIN EN 61034/DIN5510-2—other standard:
EN 50266-1 common test methods for cables under fire conditions—Test for vertical flame spread of vertically-mounted bunched wired or cables-Part 1: apparatus.
DIN EN 50266-2-4: wire and cable bundles of multiple vertical flame (cable diameter ≥ 12mm), the need for this test cables and wires (not including cable), burning the maximum damage after the test cable length of less than 2.5 m.
DIN EN 50305 section 9.1.1: wire and cable bundles of multiple vertical flame (6mm <cable diameter <12mm) the need for this test cables and wires (not including cable), combustion test cable length does not exceed the maximum damage 2.5m.
DIN EN 50305 section 9.1.2: wire and cable bundles of multiple vertical flame (diameter ≤ 6mm cable required for this test cables and wires (not including cable), burning the maximum damage after the test cable length of no more than 2.5m.
DIN EN 60332-1-2: a single vertical wire and cable flame, the need for this test cables and wires, including the data line (fiber optic cables, data bus wire, coaxial cable), combustion tests, the cable length of the top damage not more than 50mm, the bottom does not exceed 540mm.
DIN EN 61034-2: Measurement of smoke density of cables burning under defined conditions---Part 2: Test procedure and requirement.